Productdata

TYPE LG 518 GA
Product ID P11240
Medium air, non-explosive gas
Detection range air 0.5 ... 15 m/s
Process connection M18x1
Output analog output 4…20 mA
Output function non linear
Supply voltage 24 V DC +/- 20 %
Current consumption max. 100 mA
Load RL 200 ... 500 Ω
Reverse polarity protection ✓
Ambient temperature -20 ... 70 °C
Medium temperature -20 ... 70 °C
Temperature gradient gaseous media 200 K/min
Start-up time 20 ... 40 s
Reaction time typ. 3 s
Material sensor touched by medium BR-Ni, PBT
Material housing brass-Ni, PBT
Protection [EN 60529] IP 67
Electrical connection 2 m PVC-cable 3x0.5 mm²
Accessories (in scope of delivery) 2 x lock nut M18x1, screwdriver
Note with longer cable available on request

Drawings

LG 518 GA
LG 518 GA

CAD Model