SDI 852/2 GAPP
Product ID: P11321
- Flow rate sensor with amplifier
- Magnetic-inductive measuring principle
- For conductive media Measuring range 40 l/min or 80 l/min
- Flow indication with bright red 3-digit 7 segment indication
- Set-up via buttons at the device
0,2...80 l/min - 24 VDC - outputs PNP programable and analog 4...20 mA
Product request
Contact
Distribution
Do you have a question regarding sales processing, such as delivery conditions or delivery time? Click here for assistance.
Your contact person
Phone:
04346 41580
Technical support
Would you like more technical details, application advice, a replacement for a competitor's model, tips on installation or would you like to discuss possible adjustments? Please contact us!
Your contact person
Phone:
04346 41580
More about this product
Productdata
| TYPE | SDI 852/2 GAPP |
|---|---|
| Product ID | P11321 |
| Medium | water, water, water/glycol, conductive media |
| Working range electrically conductive media | 0.2 ... 80 l/min |
| Inner diameter d | 12 mm |
| Outer Diameter Pipe mm | 15 mm |
| Process connection | tube fittings for steel tubes accord. to ISO 3304 / DIN 2391 |
| Output | analog output 4…20 mA, switching output |
| Output function | PNP-NO / NC |
| Measurement error | 0...10 l/min ≤ 0,2 l/min, 10,1...80 l/min ≤ 2 % of meaurement value * |
| Supply voltage | 24 V DC +/- 10 % |
| Current consumption max. | 100 mA |
| Switching current max. | 200 mA (20 °C) |
| Load RL | 200 ... 500 Ω |
| Reverse polarity protection | ✓ |
| Ambient temperature | 0 ... 60 °C |
| Medium temperature | 5 ... 60 °C |
| Medium conductivity | ≥ 20 µS / cm ( water ≥ 30 µS / cm ) |
| Reaction time typ. | 5 ... 8 s |
| Compressive strength | 10 bar |
| Material sensor touched by medium | stainless steel AISI 316 Ti, FPM, PVDF |
| Material housing | PBT |
| Protection [EN 60529] | IP 65 |
| Electrical connection | M12 connector |
| Accessories 1 | Montageplatte |
| Accessories 2 | cable type SLG, SLW |
| Accessories 3 | Übergangsadapter G 1/4 |
| Accessories 4 | Übergangsadapter G 1/2 |
| Note | * reference conditions according to EN 29104 |