SDNC 502 GAPL

SDNC 502 GAPL

Product ID: P11381

  • Robust, compact housing from glass fibre reinforced PBT
  • Assembly in areas with minimum space
  • Set-up using IO-Link master
  • Flow rate and temperature measurement of aqueous media

G1/4 - 20...500 ml/min water - 24 VDC - output PNP programable / analog output 4...20 mA / pulse / IO-Link

Download specification CAD-Daten Request product Contact

More about this product

Productdata

TYPE SDNC 502 GAPL
Product ID P11381
Medium water
Detection range 20 ... 500 ml/min
Temperature monitoring 0 ... 60 °C
Inner diameter d 3.6 mm
Process connection G1/4
Output analog output 4…20 mA, IO-Link, pulse output, switching output
Output function PNP-NO / NC
Process data flow 0...500 [l/min x 0.001]
Process data temperature 0...600 [°C x 0,1]
Supply voltage 18 ... 30 V DC
Current consumption max. 40 mA
Switching current max. 150 mA
Load RL 200 ... 500 Ω
Reverse polarity protection ✓
Ambient temperature 0 ... 60 °C
Medium temperature 0 ... 60 °C
Reaction time typ. 0.5 ... 10 s
Programmable functions switching point, output functions, range, average value, teach-commandos
IO-Link-Specifications revision 1.1, baud rate COM 2, min. cycle time 3.5 ms, process data 4 byte
Compressive strength 10 bar
Material sensor touched by medium stainless steel AISI 316 Ti
Material housing stainless steel AISI 303, brass, PA, PBT
Protection [EN 60529] IP 67
Electrical connection M12 connector
Accessories connecting cable SLW 4-2 (Z00446), mounting bracket (Z01215), IO-Link/USB-Master-Set (Z01216)
Accessories (in scope of delivery) screw adapter

Drawings

SDNC 502 GAPL
SDNC 502 GAPL

CAD Model