MFP 075 GPP-LP030

MFP 075 GPP-LP030

Product ID: P21206

  • Precise measurement of the filling level with TDR technology
  • Programmable with digital display
  • Parallel rod probe
  • Analogue or with switching points
  • Parallel rod: Reliable measurement of media with low DK value and in plastic tanks
  • Independent of conductivity, viscosity and media consistency
  • Reliable and wear-free: no moving parts
  • For oil and media with low DK value

G3/4 - sensor length 300 mm - Output PNP programmable

Download specification CAD-Daten Request product Contact

More about this product

Productdata

TYPE MFP 075 GPP-LP030
Product ID P21206
Design parallel probe
Sensor length L 300 mm
Output switching output
Output function PNP-NO / NC
Supply voltage 20 ... 27 V DC
Current consumption max. 45 mA
Reverse polarity protection ✓
measurement accuracy 5 mm
Transition zone* top: 25 mm, bottom: 25 mm
Ambient temperature 0 ... 70 °C
Medium temperature 0 ... 80 °C
For Media with minimum DK εr ≥ 2,3
Compressive strength (at 25°C) 10 bar
Material sensor touched by medium stainless steel AISI 316 Ti, POM, PTFE
Material housing aluminium
Seal material NBR, AFM 34, other materials on request
Display digital display
Protection [EN 60529] IP67
Electrical connection M12 connector
Accessories connecting cable SLG 3... or SLW 3..., connecting cable SLG 4... or SLW 4...
Note * Transition zone: Depending on the installation conditions and the medium, deviations from the specified measuring accuracy can occur in this area.

Drawings

MFP 075 GPP-LP030
MFP 075 GPP-LP030

CAD Model